Legionella Temperature Log: What to Record and How

Published · gribit

Thermometer checking water at a basin tap

A legionella temperature log is a dated record of the water temperatures at your taps, showers and hot water cylinder, showing that hot water stays hot enough and cold water stays cold enough for legionella bacteria not to thrive. In the UK, the key readings are hot water at 50°C or above at the outlet, cold water below 20°C, and stored hot water at 60°C or above. The log only helps if each reading is taken on schedule, signed, and followed up when it is out of range. A digital logbook such as ours at Gribit keeps the schedule, the readings and the follow-ups in one place, so nothing depends on someone remembering to find a clipboard.

Gribit
Keep Recurring Safety Checks Organised
Gribit brings recurring check records, follow-ups and certificates together in a digital logbook for small businesses.
Visit

TL;DR

  • Hot water should reach at least 50°C at the tap within one minute, cold water should be below 20°C after two minutes, and stored hot water should be at 60°C or higher.
  • Check sentinel outlets (the taps nearest and furthest from each tank or cylinder) monthly, cylinders monthly, and cold water tanks at least every six months.
  • Each entry needs the outlet, the reading, the date, who took it and any corrective action.
  • Keep monitoring records for at least five years.
  • A recurring digital check with reminders and a follow-up list is easier to keep up than a paper sheet that depends on one person.

Table of Contents

Who needs to keep a legionella temperature log

Legionella is the bacterium behind Legionnaires’ disease, a serious lung infection caught by breathing in tiny droplets of contaminated water, for example from a shower. GOV.UK’s guidance on safe water supplies lists the kinds of organisation that need to act on the risk, including hairdressers, hotels, gyms, sports clubs and office buildings, especially those with shower facilities. It also notes that Legionnaires’ disease is fatal in around 10% of cases, and that water systems which are shut down or little used need regular flushing.

If you run a pub, a salon, a village hall or a small office, you have the same duty as a large site: assess the risk from your water system and keep it under control. The size of your premises changes the amount of work, not the duty.

The law on records depends on headcount. HSE says that if you have five or more employees you must record the significant findings of your risk assessment. With fewer than five you do not have to write anything down, though HSE says a written record is still useful. In practice, a temperature log is the simplest way to show that the controls in your risk assessment are actually being carried out. If a village hall committee changes every few years, or a salon has a new manager, a log is also what lets the next person see what has been done.

If you employ five or more people, our guide to what goes in a health and safety file for small sites shows where water records sit alongside your other paperwork.

The temperatures your log should be checking

The temperatures your log should be checking

Water temperature control is the main way legionella risk is managed. HSE explains that the bacteria multiply between 20°C and 45°C, stay dormant below 20°C and do not survive above 60°C. So the aim is to keep hot water hot and cold water cold.

These are the figures that matter for a typical small site:

Where What to check Target
Hot water cylinder (calorifier) Stored or outgoing water 60°C or higher
Hot water at the tap After running for 1 minute 50°C or higher
Cold water at the tap After running for 2 minutes Below 20°C
Pipework feeding thermostatic mixing valves (TMVs) Hot water supply to the valve 50°C or higher
Cold water storage tank Temperature at the ball valve outlet Below 20°C

A calorifier is simply the hot water storage cylinder. A TMV is a valve that blends hot and cold water to stop scalding, often fitted to showers and basins. The stored-water figure comes from HSE’s guidance on hot and cold water systems, and the one-minute and two-minute run times come from HSE’s list of things to consider. HSG274 Part 2, HSE’s technical guidance, repeats these and adds that in healthcare premises hot water should reach 55°C rather than 50°C. If your premises is a care setting or similar, follow your risk assessment on that point.

Why the run time matters

Water sitting in a pipe warms or cools to the room temperature, so a reading taken the moment the tap opens tells you nothing about the system. The reading that counts is the one taken after the water has run for the set time. That is why a good log has a column for how long the tap ran, or at least a fixed routine that everyone follows. If one person runs the tap for ten seconds and another for two minutes, you cannot compare the readings.

Which outlets to check, and how often

You do not need to test every tap every month. HSE’s approach is to check a few carefully chosen points often, and the rest in rotation.

Sentinel outlets: monthly

Sentinel outlets are the taps or showers closest to and furthest from each tank or cylinder. They are the places where the water is most likely to be too warm or too cold, so they act as an early warning for the whole system. HSE says you must identify them and check distribution temperatures there monthly, and check hot water cylinder temperatures every month.

For a small pub that might mean the first and last tap on the hot water run, say the cellar sink nearest the cylinder and the upstairs bathroom furthest from it. In a small salon it could be the basin nearest the boiler and the staff kitchen at the far end. Eden Council’s business guidance puts it the same way: first and last tap on the run, monthly.

Representative outlets: in rotation

Other outlets are checked on a rotational basis, so that over a year every tap or shower has been checked at least once. HSE’s guidance describes this, and Eden Council describes annual rotational checks for hot water at 50°C within one minute and cold water below 20°C after two minutes. HSG274 Part 2 adds that temperature profiling at representative outlets is a useful way to confirm that safe temperatures are being kept in all parts of the system in normal use.

Tanks, showers and quiet outlets

  • Cold water tank: check the temperature at least every six months, at the ball valve outlet, and look inside for debris, a loose lid or missing insulation.
  • Little-used taps and showers: HSE advises flushing them at least weekly, because stagnant water is where bacteria build up.
  • Shower heads and hoses: clean and descale them at least quarterly.
  • Dead legs: pipework that no longer serves anything should be removed.

Those flushing and cleaning jobs are not temperature readings, but they belong in the same log, because the same inspector will ask for both. A village hall that is used twice a week is a classic case: the showers and kitchen taps sit unused for days, and weekly flushing is the control that matters.

Frequency at a glance

Check How often
Sentinel outlet temperatures Monthly
Hot water cylinder temperatures Monthly
Other outlets Rotating, so each is checked at least yearly
Cold water tank temperature At least every 6 months
Flushing rarely used outlets At least weekly
Cleaning and descaling shower heads and hoses At least quarterly

Your own risk assessment may set a different frequency, and it overrides these general figures. If a competent person wrote it for you, follow it.

What each log entry should contain

HSG274 Part 2 says records should hold accurate information about who did the work and when, be signed or authenticated, and include the results of checks and any corrective action. Turned into a practical entry, that means:

  1. Date and time of the reading.
  2. Outlet name or location, for example Gents basin, first floor, or Shower 2.
  3. Hot or cold and which type of outlet it is (sentinel or rotational).
  4. Run time before the reading, 1 minute for hot and 2 minutes for cold.
  5. Temperature reading in °C.
  6. Pass or fail against the target.
  7. Who took it, by name.
  8. Action taken and the date it was closed, if the reading was out of range.

A worked example: on the first Monday of the month, Priya runs the hot tap in the staff toilet furthest from the cylinder for one minute and reads 47°C. The target is 50°C, so the entry is a fail. She writes the action: reported to the manager, who asks the heating engineer to check the cylinder thermostat and the pipework. When the engineer has been, the entry is closed and the tap is retested. Without those last lines the log shows a problem but no response, which is the weakest kind of record.

If you want guidance on writing entries that stand up when someone reads them months later, our guide on how to write a logbook entry for safety checks covers the habits that make a record useful.

What to do when a reading is out of range

A failed reading is not a disaster; an unrecorded one is. Take these steps:

  1. Record the reading as it was. Never adjust a figure to make it look right.
  2. Recheck after a short time, to confirm it is not a one-off, for example caused by a tap that had not run long enough.
  3. Report it to the person responsible for your water risk assessment, whether that is you, a manager or an outside competent person. HSE says a competent person should routinely check, inspect and clean the system, and that is who decides the fix.
  4. Log the cause and the fix, such as a cylinder thermostat reset, a repaired valve or a flushed dead leg.
  5. Retest and record the new reading, so the log shows the problem closed.

If you suspect legionella may be present, or someone who uses the premises has been diagnosed with Legionnaires’ disease, speak to your competent person or water hygiene specialist straight away and contact your local authority environmental health team. Water sampling for legionella bacteria is separate from temperature checks. HSE says samples should be analysed periodically, with the frequency set by your risk assessment.

How long to keep the records

HSE’s records page says records should be kept for the period they remain current and for at least two years afterwards. Records of monitoring and inspection, which is what a temperature log is, should be kept for at least five years. HSG274 Part 2 says the same.

Five years of monthly readings across several outlets is a lot of paper. It is also a long time for a ring binder to survive a refit, a change of manager or a leaking cellar. Certificates, such as a legionella risk assessment or a water hygiene contractor’s report, need to be kept with the log for the same reason: they are the evidence that the log refers to.

Paper log or digital logbook?

A paper template does the job if it is filled in every month. The common failures are practical rather than technical: nobody remembers the due date, the sheet is in the wrong building, the person who took the readings has left, and a failed reading sits on a page with no one assigned to fix it.

A digital logbook removes those failures. In ours, you set the check up once as a recurring task, and we send reminders when it falls due. Each check can be organised by site, item or location, so a particular outlet or cylinder has its own history. You can give staff access so more than one person can record a reading, add the engineer’s certificate alongside the entry, track follow-up actions until they are closed, and export the records when someone asks to see them. The comparison is set out in more detail in our guide to paper versus digital logbooks.

Paper logbook problems compared with digital controls

Water temperatures are one of several recurring checks you probably already run. Fire alarm tests have their own weekly rhythm, covered in our fire alarm test frequency guide, and electrical items run on a different cycle again, as the guide to PAT testing frequency in England explains. Keeping all of these on the same calendar and in the same record is easier than keeping a separate binder for each.

HSE also notes that remote monitoring systems using temperature sensors can check a system more often than manual readings. HSG274 Part 2 advises that their use should rest on your specific legionella risk assessment and be agreed by a competent person. If you are considering sensors, raise it with whoever wrote your assessment.

Setting up your log in five steps

  1. List your outlets and mark the sentinels. Walk the site with your risk assessment. Note every tank, cylinder, TMV, tap and shower, and mark the nearest and furthest outlet for each cylinder.
  2. Set the schedule. Monthly for sentinels and cylinders, six-monthly for cold water tanks, weekly for flushing, quarterly for shower heads, and a rotation for the rest.
  3. Choose who records. Name a person and a backup, so that holidays do not break the monthly routine.
  4. Agree the fail rule. Write down who is told when a reading is out of range and how quickly it must be looked at.
  5. Keep the paperwork with the log. Risk assessment, contractor reports and any remedial work receipts belong in the same place for at least five years.

A useful habit is to walk the site once and take the readings in the same order every month. Our safety walk checklist shows how to fold this kind of round into a broader routine for small sites.

Our view on legionella records

Most small sites we think about do not fail on legionella because nobody cares. They fail because a monthly job has no owner and no reminder. The temperature itself takes a minute to read. The hard part is remembering, recording it the same way each time, and making sure a bad reading leads to a fix that someone can later see.

That is why we built Gribit around the recurring check rather than the form. A check that comes due on its own, that anyone with access can complete, and that keeps its follow-up actions and certificates beside the reading, turns a pile of paper into a record you can hand to an inspector or a new manager without a scramble.

For a pub, a salon, a village hall or a small office, one site subscription covers the whole routine: temperatures, flushing, fire checks, first aid kits and the documents that go with them.

Jon

Keep your legionella log in Gribit

Our Site Logbook is an annual plan at £49 per site per year. You set up your recurring checks, record results, manage follow-up actions, store certificates and documents, give staff access and export your records when needed.

Gribit

If your legionella checks currently live on a sheet of paper, start your site logbook at Gribit and put the monthly readings on a schedule that reminds you.

FAQ

Do I legally have to keep a legionella temperature log?

The law requires you to assess and control the legionella risk, and HSE says employers with five or more staff must record the significant findings of the risk assessment. With fewer than five you need not write anything down, but HSE says it is useful to. A temperature log is the usual way to show the controls are working.

What temperature should a hot tap be for legionella control?

Hot water should reach at least 50°C at the outlet within one minute of running, and stored hot water should be at 60°C or above. Cold water should be below 20°C after two minutes. These are HSE’s figures, and your risk assessment may add to them.

How often should I take readings?

Sentinel outlets and hot water cylinders are checked monthly, and cold water tanks at least every six months. Other outlets are checked in rotation, so each is covered at least once a year. Little-used taps and showers should be flushed at least weekly.

How long should I keep the log?

Monitoring and inspection records, which includes temperature readings, should be kept for at least five years, according to HSE. Other legionella records should be kept while current and for at least two years afterwards.

Is a spreadsheet or paper sheet good enough?

HSE does not require a particular format, only accurate records showing who did what and when, with results and corrective actions. A digital logbook makes it easier to meet that standard consistently, because reminders, staff access, follow-ups and certificates sit with each reading.